Gas Gensets / kVA - kVA / TJ275DW-NG5A
|
|
|
| Power Output Ratings |
| |
|
50 Hz |
60 Hz |
| Standby Power (ESP) |
kVA |
273 |
X |
 |
 |
 |
| kW |
218 |
X |
 |
 |
 |
 |
| Prime Power (PRP) |
kVA |
246 |
X |
 |
 |
 |
| kW |
197 |
X |
| Engine |
| |
|
50 Hz |
60 Hz |
| Manufacturer |
|
DOOSAN |
 |
 |
 |
| Origin |
|
KOREA |
 |
 |
 |
| Model |
|
GV158TIR |
 |
 |
 |
| No of Cylinder / Configuration |
|
8 - V TYPE |
 |
 |
 |
| Displacement |
lt |
14,618 |
 |
 |
 |
| Bore / Stroke |
mm |
128 / 142 |
 |
 |
 |
| Compression Ratio |
|
10,5:1 |
 |
 |
 |
| Aspiration |
|
Turbocharged and Intercooled(Water to Air) |
 |
 |
 |
| Governor Type |
|
ELECTRONIC |
 |
 |
 |
| Cooling System |
|
WATER |
 |
 |
 |
| Coolant Capacity |
lt |
192,3 |
 |
 |
 |
| Lubrication Oil Capacity |
lt |
31 |
 |
 |
 |
| Electrical System |
VDC |
24 |
 |
 |
 |
| Speed / Frequency |
|
1500 rpm / 50 Hz |
X |
 |
 |
 |
 |
| Engine Gross Power |
kWm |
253 |
X |
 |
 |
 |
 |
| Fuel Consumption (Nm³/h) |
110 % |
63,2 |
X |
| 100 % |
58,4 |
X |
| 75 % |
48,2 |
X |
| 50 % |
39 |
X |
 |
 |
 |
 |
| Exhaust Outlet Temperature |
°C |
495 |
X |
 |
 |
 |
 |
| Exhaust Gas Flow |
m³/min |
30 |
X |
 |
 |
 |
 |
| Combustion Air Flow |
m³/min |
18,5 |
X |
 |
 |
 |
 |
| Cooling Air Flow |
m³/min |
550 |
X |
| Alternator |
| |
|
50 Hz |
60 Hz |
| Manufacturer |
|
MARELLI |
 |
 |
 |
| Origin |
|
ITALY |
 |
 |
 |
| Model |
|
MJB315SA4 |
 |
 |
 |
| Power Factor |
|
0,8 |
 |
 |
 |
| No of Phase |
|
3 |
 |
 |
 |
| No of Bearing |
|
SINGLE |
 |
 |
 |
| No of Poles |
|
4 |
 |
 |
 |
| No of Leads |
|
12 |
 |
 |
 |
| Voltage Regulation ( Steady State) |
|
± %0,5 |
 |
 |
 |
| Insulation Class |
|
H |
 |
 |
 |
| Degree of Protection |
|
IP 23 |
 |
 |
 |
| Excitation System |
|
AVR (Automatic Voltage Regulator), Brushless |
 |
 |
 |
| Connection Type |
|
STAR |
 |
 |
 |
| Total Harmonic Content (No Load) |
% THD |
< %2 |
 |
 |
 |
| Frequency |
Hz |
50 |
60 |
 |
 |
 |
 |
| Voltage Output |
VAC |
230 / 400 |
X |
 |
 |
 |
 |
| Rated Power (Standby) |
kVA |
330 |
X |
 |
 |
 |
 |
| Efficiency |
% |
93,1 |
X |
| Dimensions |
| |
W x L x H (mm) |
Weight (kg) |
Fuel Tank (lt) |
| Canopied |
1650 x 4500 x 2350 |
3200 |
N/A |
 |
 |
 |
 |
| Open Skid |
1650 x 3500 x 1850 |
2450 |
N/A |
|
|
Standby Power
Standby power is defined as the maximum power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage or under test conditions for up to 500 hours of operation per year under average of 70% load. Overloading is not permissible.
Prime Power
Prime power is defined as being the maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load. Average load should be 70%. The generator can be overloaded 10% for 1 hour per 12 hours.
|
|
|
|
|